Multi-channel alarm controller system for combustible and toxic gas monitoring

Multi-channel alarm controller system for combustible and toxic gas monitoring
Product Detailed
Alarm controller Multi channels & 2/3-wire system LED display concentration Two alarm point for each unit 100 alarm records

Multi-channel alarm controller system for combustible and toxic gas monitoring

 KB-2000B (2/5/10)

Performance and features

1) Wall-mounted & multi-circuits alarm controller, available to connect with two-wire & three-wire gas detector

2) LED display concentration easy for watch

3) Can set two alarm points value seperately

4) 100 alarm memories

5) Time clock can running at backstage and make the screen more clear

6) Can receive any 4-20mA signal

 

Product introduction

KB-2000B series alarm controller system for combustible gas detection is a new type design according to the national standard; this alarm controller is mainly applied to petroleum & chemical industry, medicine and city gas, pipeline of delivery for oil gas and the transfer station etc fields with the combustible gas.

This equipment applies digit technique with high IC smart instrument. It’s controlled by the computer from signal collection, alarm control to alarm display; in the system applies specified time clock chip so that the precise timing when cut of the power and save the alarm signal for 100 records, all the information including time, concentration, alarm setting point, time of alarm and records are displayed by 4 units LED screen. 

This alarm controller can monitor the detector working condition from 1 to 10 circuits and can display the status of working, fault, low concentration alert and high concentration alert. It can sound different audible signals between fault and alarm so that reminder the operator to handle it by way of keyboard, adjustable time and alarm concentration and it has the functions of self-checking, erasure and resetting.

The standby battery is available and can still work more than 2 hours when cut off the power.

Technical parameters:

Type of controller

KB-2000B

Panel point output

5A@220AC

Detection circuits

2/5/10 channels (optional)

Power supply

220V/ AC

Display model

4 units LED

Alarm power consumption

less than145W

Size

350X240X110MM

Kinds of gas

ppm; LEL; % vol

Signal input

4-20mA

Alarm concentration

Two alarm setting available (adjustable)

Adjustable mode

Keyboard or key lock

Atm press

86~106KPa

Relative humidity

10~90%RH

Storage temperature

-20°C~+40°C

operating temperature

0~+40°C

Alarm volume

more than 90dB

Indicate accuracy

1%

Installation mode

Wall mounted installation

Order guide

Model

Installation mode

Channel of Detection

Input signal

Output of RS-485

KB-2000B(2)

Wall mounted installation

2 channels

4-20mA

no

KB-2000B(5)

Wall mounted installation

5 channels

4-20mA

no

KB-2000B(10)

Wall mounted installation

10 channels

4-20mA

no

Standard configuration

key; keyboard key; user manual; certificate of quality; safe tube